01 / OVERVIEW
Construction sites need power that is dependable, easy to deploy and capable of supporting changing loads. But many generators are sized for occasional peaks and spend much of the day operating below their most efficient range.
ChargeHives™ provide mobile battery power for temporary construction applications. They can operate from available utility service, renewables, or alongside a generator, supplying jobsite loads while reducing generator runtime, fuel consumption, noise and maintenance.
​
This allows temporary power capacity to be matched more closely to the jobsite’s actual load profile and operating schedule. This brief outlines how ChargeHives™ can support construction and temporary-power applications through grid-supported, generator-hybrid and stand-alone configurations.

Figure 1: HiveCore™ Peer to Peer Mode Configuration (Pennington, NJ)
02 / DEPLOYMENT
How ChargeHives™ are Deployed on Construction and Job Sites
ChargeHive™ deployment is based on the site’s available power source, load profile and required operating duration. The system can be configured around three common temporary-power conditions.
​
Limited Utility Power: ChargeHive™ supplements temporary utility service when the available connection cannot support the site’s full or peak demand. The system recharges when demand is lower and supplies additional power when loads increase.​
Best suited for: Utility-constrained sites, temporary electrical service and projects awaiting a larger permanent connection.
Generator Hybrid: A smaller generator operates at a more efficient load level while supplying power and recharging the ChargeHive™. The ChargeHive™ supports changing loads, short-duration peaks and periods when the generator can be turned off.
Best suited for: Off-grid sites, intermittent equipment loads, oversized generators and projects with extended low-load operation.
​
Stand-Alone Mobile Power: A pre-charged ChargeHive™ supplies a defined shift, work period or temporary load without an operating generator. The unit can then be recharged from an available electrical source or relocated for charging.
Best suited for: Short-duration work, nighttime operations, indoor or noise-sensitive areas and locations where local generator emissions are undesirable.
Limited Utility Power
GRID-SUPPORTED CONFIGURATION

UTILITY
CHARGEHIVE
SITE LOADS
ChargeHive supplements temporary utility service when the available connection cannot support the site's full or peak demand.
BEST FIT
Limited service, temporary connections and peak loads
Generator Hybrid
HYBRID CONFIGURATION

GENERATOR
CHARGEHIVE
SITE LOADS
A smaller generator supplies power and recharges the ChargeHives. The battery supports changing loads, peaks, and generator off-periods.
BEST FIT
Off-grid sales and intermittent equipment loads
Stand-Alone Mobile Power
BATTERY-ONLY CONFIGURATION

CHARGEHIVE
SITE LOADS
A pre charged ChargeHive supplies a defined shift or work period without an operating generator at the point of use.
BEST FIT
Short-duration, nighttime, or sensitive locations
03 / SITE PROFILE & OPERATION
24/7 Remote Construction Compound
24-Hour Daily Load Profile
DAILY ENERGY
390 kWh
AVERAGE LOAD
16.25 kW
PEAK LOAD
170 kWh
Operating period
Duration
Demand
Daily Energy
Baseline Operations
18 hours
10 kW
180 kWh
Active Operations
5.5 hours
22.7 kW
125 kWh
Peak
0.5 hour total
170 kW
85 kWh

24/7 Construction Site Profile
Project
Remote construction compound
Supported loads
Trailers, lighting, security, communications, pumps, hoists and intermittent equipment
Electrical service
480 V, three-phase
Baseline demand
10 kW for 18 hours/day
Active work period
6 hours/day
Average active-period demand
35 kW
Peak demand
170 kW
Peak duration
Two 15-minute events per day
Average daily demand
16.25 kW
Daily energy demand
390 kWh
Opearting schedule
24 hours/day, 7 days/week
Annual operating days
365 days
Existing generator
200 kW prime diesel generator
Existing generator operation
Continuous, 24 hours/day
Existing fuel consumption
50.5 gallons/day
Diesel price
$5.50/gallon
Replacement gen
56 kW prime diesel generato
ChargeHive
HiveCore, 260 kWh / 140 kW PCS
Battery round-trip efficiency
90%
Operating Condition
System Response
Demand below 56 kW
Generator supplies the load and uses available capacity to charge HiveCore
Demand above 56 kW
HiveCore supplements the generator and supplies the difference
Peak demand up to 170 kW
The 56 kW generator and HiveCore operate together; HiveCore supplies up to approximately 114 kW
Low-demand and overnight periods
Battery reserve is reached
HiveCore can supply the 10 kW baseline while the generator is off
Generator restarts and supplies the load while recharging the battery
For this generator-hybrid application, a HiveCore™ is paired with a 56 kW prime diesel generator in place of the existing 200 kW generator. The generator supplies sustained site demand and recharges the battery whenever its available output exceeds the active load. HiveCore™ supplements the generator during higher-demand periods, including construction-hoist operation and site peaks up to 170 kW. During lower-demand periods, stored energy can supply the site while the generator is turned off. This configuration provides on-site battery charging without requiring a separate utility connection or taking the system out of service to recharge.
04 / RESULTS
Operating and Cost Impact
Cost Assumption
Generator configuration
Generator rental
HiveCore rental
Diesel price
Generator runtime
Fuel consumption
TOTAL ANNUAL SAVINGS
$25,351
Estimated direct operation savings
GENERATOR TIME REDUCTION
69%
Per month
Conventional
200 kW generator
$7,000/month
Not applicable
$5.50/gallon
24 hours/day
50.5 gallons/day
MONTHLY EQUIVALENT SAVINGS
$2,113
Per month
DIESEL AVOIDED ANNUALLY
7,300
Gallons, approximately
Hybrid
Remote construction compound
$2,000/month
$6,250/month
$5.50/gallon
Approximately 7.4 hours/day
30.4 gallons/day
FUEL REDUCTION
40%
Approximately
GENERATOR HOURS REDUCTION
6,050
Hours annually, approximately
Costs are based on specific equipment rental rates, manufacturer fuel-consumption data and the modeled site load profile. Actual performance and pricing will vary by project, equipment configuration and location.